Radar boundary bleed: capping range at the room edge

Radar range does not stop at a partition wall. Map the boundary first, then choose a gate cap, a rectangular zone or a detection area.

The boundary is a detection problem

A module's published range is not a room boundary. A person in the next room can return enough energy to sit inside the same detection gate as a person in this room. Hi-Link lists thin walls and metal reflections among the installation conditions for its presence modules. Seeed lists glass and thin wooden boards for the MR60FDA2, and DFRobot lists reflective surfaces for the C1001.

Those pages describe conditions, not attenuation figures. There is no useful "radar sees through 12 cm of this material" number to design against, because the result depends on the wall, the angle, the target and the firmware thresholds. The practical approach is to measure the boundary in the room and then constrain the module with the control it actually exposes.

Map the boundary in the sensor's own coordinates

The three common module families expose different geometry, so the same room needs a different description for each.

Module family Geometry exposed Boundary control
LD2410 Range gates 0 to 8, no angular coordinate Maximum move and still distance gate
LD2450 x from -3000 to 3000 mm, y from 0 to 6000 mm Up to three rectangles, plus a Detection or Filter mode
LD6002B x, y and z areas relative to a floor or wall origin Detection areas and interference areas

For the LD2450, the rectangle runs from x1, y1 at the near-left corner to x2, y2 at the far-right corner, all in millimetres. A zone that covers the room but stops at the wall is therefore a coordinate problem, not a sensitivity problem. For the LD6002B, the reference plane is the floor for a ceiling install and the wall for a side install, with X left and right, Y forward and Z height. For the LD2410, there is no x coordinate at all; the only boundary control is which gate index is the last one allowed to contribute.

Three controls, three different contracts

The controls are not interchangeable. Each one changes a different output.

The LD2410 maximum move distance gate and maximum still distance gate accept a value from 2 to 8 and default to 8. Gates above the cap stop contributing to motion or still detection. Each gate also has its own move and still threshold from 0 to 100.

The LD2450 exposes zone_1 to zone_3 as rectangles and a zone_type select with Disabled, Detection and Filter. Disabled turns zone area detection off. Detection considers only targets in the specified area, and Filter excludes an area from detection. The zone entities report target_count, still_target_count and moving_target_count inside each rectangle.

The LD6002B detection areas define where presence is considered valid for the TX2 output and for the detection_area_N binary sensors. Its interference areas mask known noise sources such as fans, air conditioners and curtains. Both area types are stored in the module and survive a power cycle.

Control What it changes What to verify before relying on it
LD2410 maximum gate Which gates can trigger motion or stillness The reported gate index at the real boundary
LD2450 zone rectangles Per-zone target counts Whether your automation uses zone counts or the presence flag
LD2450 zone_type Whether zones include or exclude an area That zone detection is not left Disabled
LD6002B detection area Where presence is valid for TX2 and area entities The area's origin and axis directions
LD6002B interference area Which known noise sources are masked That the mask does not cover a real walking path

One warning matters more than the rest. The LD2450 presence binary sensors are described as presence states for the targets, while the zone entities are described as target counts inside the defined zones. Do not assume that setting a Filter zone also filters has_target on your firmware. If the automation needs a room-only flag, build it from the zone target counts and verify the behaviour on the bench.

Tune the boundary, not the global sensitivity

Take three readings: an empty room with the fan and HVAC off, the same room with them running, and a person sitting at the boundary position that matters. Set the per-gate thresholds between the second and third readings, then cap the last gate at the wall.

The LD2410 defaults explain why a default install can reach too far. Gate 8 is enabled by default, and the default still thresholds at gates 6, 7 and 8 are 20, 20 and 20, not zero. A far reflection therefore has a path into the presence decision until the gate cap or the thresholds remove it.

Lowering a global sensitivity value is not a boundary control. It usually moves the false trigger to another distance while also making the intended position less reliable.

Validate from the other side of the wall

Stand in the adjacent room, walk along the shared wall and watch the presence output. Then walk the far corner of the intended room and confirm the module still sees a person there. A cap that passes the first test and fails the second is too aggressive.

Record the module, firmware, mounting height, gate cap or zone coordinates, and the readings for all three cases. A re-mount or a firmware update changes the geometry, so an earlier baseline is not reusable without re-checking.

No device was bench tested for this chapter. The settings above are documented controls and defaults; the boundary values have to be measured in the actual room.